Direct import from European stocks — no middlemen · 10 partner stocks · −30 to −50 % vs retailFRENDENLESIT
Installation & advice Blog Showroom Made to measure Customer stories Trade area →

Sizing hot-water radiators: the method

Watts per m³ by insulation level, delta T, position under the window, bleeding and balancing: sizing radiators right in renovation.

Radiateur à eau chaude avec robinet thermostatique sous fenêtre

An undersized radiator heats continuously without ever getting there; oversized, it costs money and cycles. Sizing takes three minutes per room — here is the heating engineers' simplified method.

Power per room

Home insulation Indicative power
Old, uninsulated ≈ 100 W/m³… insulate first!
1990s-2000s renovation ≈ 70-85 W/m³
Well renovated (walls R ≥ 3.7, loft R ≥ 7) ≈ 40-60 W/m³

Example: 12 m² bedroom × 2.5 m = 30 m³, well-renovated home → 30 × 50 = 1,500 W. Add ~10 % for a north façade or corner room.

Delta T: reading labels without being fooled

Catalogue output is given at ΔT50 (water at 70/50 °C). With a heat pump or low-temperature condensing boiler (ΔT30), the same radiator delivers only ~50 %: you must therefore oversize by about half on a heat pump — or switch to underfloor heating, built for low temperatures.

Placement (diagram)

windowradiator under the window10-15 cm off the floor, 3-5 cm off the wall — it counters the cold downdraught from the glassnever hidden bycurtains or boxing

The finishing touches that change everything

  • Thermostatic valves everywhere except the room with the main thermostat.
  • Balancing: lockshield valves throttled on radiators close to the boiler, or the far rooms stay cold.
  • Bleed every autumn; sludge → power-flush every 8-10 years.
  • Fixing: a full 1,500 W steel radiator weighs 30-45 kg — on plasterboard, see fixing heavy loads.

Leave a Reply

Your email address will not be published. Required fields are marked *

Do you want to check stock availability?
Instant reply on WhatsApp.
Check on WhatsAppCall us